Siemens SINAMICS S120 Manual page 223

Cabinet modules liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Article No.
Current consumption
- Total operating current, 3 AC 400 V, 50/60 Hz
- Electronics current (24 V DC)
Power consumption, max., 3 AC 400 V,
50/60 Hz
Power loss, max., dissipated to the ambient air
4)
Sound pressure level L
pA
Material of the integrated heat exchanger
Degree of protection (standard version)
Dimensions (standard version)
- width
- height
- depth
Weight, approx. (standard version)
Depending on the ambient temperature and humidity, see Chapter "Protection against condensation" in Section "Com-
1)
missioning the cooling circuit".
This value applies to the water coolant option; for other coolant types, see Chapter "Cooling circuit and coolant proper-
2)
ties".
0 °C with antifreeze.
3)
The specified power loss represents the maximum value at 100 % utilization. The value in normal operation is lower.
4)
With option W01, the cabinet width increases to 1000 mm.
5)
With option W01, the cabinet weight increases by approximately 110 kg.
6)
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A
6SL3705-
A
A
kW
kW
(1 m) at 50/60 Hz
dB(A)
mm
mm
mm
kg
0RE23-
0RE24-
2AA5
8AA5
7.5/7.0
7.5/7.0
1.0
1.0
3.5/4.7
3.5/4.7
0.5
0.5
<65
<65
Stainless
Stainless
steel
steel
IP55
IP55
600
600
5)
5)
2200
2200
600
600
310
310
6)
6)
Cabinet Modules
6.4 Heat Exchanger Modules
0RE27-
0RE31-
2AA5
1AA5
11.0/12.0
11.0/12.0
1.0
1.0
5.5/6.4
5.5/6.4
0.5
0.5
<65
<65
Stainless
Stainless
steel
steel
IP55
IP55
600
600
5)
5)
2200
2200
600
600
320
320
6)
6)
221