K82, Terminal Module For Activating Safety Functions "Safe Torque Off" And "Safe Stop 1 - Siemens SINAMICS S120 Equipment Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Options

8.12 K82, terminal module for activating safety functions "Safe Torque Off" and "Safe Stop 1"

8.12
K82, terminal module for activating safety functions "Safe Torque Off"
and "Safe Stop 1"
Availability of option
This option is available for the following S120 Cabinet Modules:
● Motor Module in chassis format
● Booksize Cabinet Kit
Description
The option K82 (terminal module for activating "Safe Torque Off" and "Safe STOP 1") is
used for isolated activation via a variable control voltage range of the safety functions
already present in the standard, which can also be used without option K82.
Use option K82 to activate the following Safety Integrated functions (terminology according
to draft IEC 61800-5-2):
● Safe Torque Off (STO)
● Safe Stop 1 (SS1, time-controlled)
Note
The integrated safety functions, starting from the Safety Integrated (SI) input terminals of the
SINAMICS components (Control Unit, Motor Module), satisfy the requirements of Machinery
Directive 98/37/EC, EN 60204-1, and DIN EN ISO 13849-1 category 3 (formerly EN 954-1),
as well as the requirements for Performance Level (PL) d and IEC 61508 SIL2.
In combination with option K82, the requirements specified in Machinery Directive 98/37/EC,
as well as in EN 60204-1 and DIN EN ISO 13849-1 category 3 (formerly EN 954-1) are
satisfied for Performance Level (PL) d and IEC 61508 SIL2.
Note
Detailed and comprehensive instructions and information for the Safety Integrated functions
can be found in the accompanying operating instructions, which are available as additional
documentation on the enclosed customer CD.