Options
8.14 L08/L09, motor reactor / 2 motor reactors in series
Motor connection
On Booksize Cabinet Kits with option L08 / L09 installed, the motor cables are connected to
terminal block -X2 (with a Double Motor Module: -X2, -X4).
Table 8- 19
Order no. : 6SL3720-
2TE13-0AB0
2TE15-0AB0
2TE21-0AB0
2TE21-8AB0
1TE13-0AB0
1TE15-0AB0
1TE21-0AB0
1TE21-8AB0
1TE23-0AB0
1TE24-5AB0
1TE26-0AB0
1TE28-5AB0
1TE31-3AB0
1TE32-8AB0
368
Maximum conductor cross section when using motor reactors for Booksize Cabinet Kits
Power in kW
2 x 1.6
2 x 2.7
2 x 4.8
2 x 9.7
1,6
2,7
4,8
9,7
16
24
32
46
71
107
Maximum connection cross section
6 mm²
6 mm²
6 mm²
6 mm²
6 mm²
6 mm²
6 mm²
6 mm²
6 mm²
16 mm²
16 mm²
35 mm²
95 mm²
95 mm²
S120 Cabinet Modules Equipment Manual