Connecting The Pe Busbar In Accordance With The Plant-Side Grounding Concept; Connecting External Cables To The Pe Busbar - Siemens SINAMICS S120 Equipment Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4.5.1.3

Connecting the PE busbar in accordance with the plant-side grounding concept

Once you have established the connections to the PE busbar in the cabinet and/or
established the connections to the PE busbar across more than one cabinet unit, you must
establish a connection to the central ground of the entire system.
4.5.1.4

Connecting external cables to the PE busbar

CAUTION
When external cables that are to be connected to the PE busbar have been laid, make sure
that the cabinet doors close properly.
Preparatory steps
● Install and secure the cabinet units properly.
● Disconnect the cabinet units from the power supply.
● Make sure that all the necessary safety measures have been taken at the installation
● Observe the "five safety rules".
● Allow unimpeded access to the PE busbar of the cabinet units (if necessary, remove the
Establishing the connection
1. Insert the screw from the front.
2. Attach the cable lug from behind.
3. Attach the nuts and, if necessary, the washers and tighten
S120 Cabinet Modules Equipment Manual
Manual, (GH5), 10/2008, A5E00427098A
DANGER
location.
protective covers).
(torque: 50 Nm).
Electrical installation
4.5 Connections
59