Active Line Modules; General Information; Description - Siemens SINAMICS S120 Equipment Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Cabinet Modules

5.4 Active Line Modules

5.4
Active Line Modules
5.4.1

General information

Hazardous voltages are present in certain parts of this equipment during operation of the
cabinet unit.
Only qualified personnel may work on the cabinet.
Such personnel must be thoroughly familiar with all the warnings and maintenance
procedures for the cabinet described in the documentation provided.
The successful and safe operation of this cabinet is dependent on correct transport, proper
storage and installation, as well as careful operation and maintenance.
National safety regulations must be observed.
5.4.2

Description

Note
Refer to the layout diagrams and circuit diagrams provided on the enclosed customer CD for
the arrangement of components and interfaces, and for wiring.
Active Line Modules can supply motoring energy and return regenerative energy to the
supply system.
Active Line Modules generate a regulated DC voltage that is kept consistent regardless of
fluctuations in the line voltage (the line voltage must range within the permissible tolerances).
In the factory setting, the DC voltage is regulated to 1.5 times the rms value of the rated line
voltage.
Active Line Modules draw a virtually sinusoidal current from the supply system and cause
virtually no line harmonic distortions.
Active Line Modules are available for the following voltages and power ratings:
Line voltage
380 ... 480 V 3 AC
500 ... 690 V 3 AC
The power rating can be increased by connecting Active Line Modules in parallel.
148
DANGER
Rated power
132 ... 900 kW
560 ... 1400 kW
S120 Cabinet Modules Equipment Manual
Manual, (GH5), 10/2008, A5E00427098A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics s120 cabinet module

Table of Contents