Cabinet Modules
5.2 Basic Line Modules
Voltage derating as a function of the installation altitude
In addition to current derating, voltage derating must also be considered at installation
altitudes > 2000 m above sea level.
Table 5- 21
Table 5- 22
Note
On systems with a grounded phase conductor and a line voltage > 600 V AC, measures
must be taken on the line side to limit overvoltages to overvoltage category II in accordance
with IEC 60664-1.
134
Voltage derating as a function of the installation altitude (380 to 480 V 3 AC)
Installation altitude
above sea level in m
0 to 2000
up to 2250
up to 2500
up to 2750
up to 3000
up to 3250
up to 3500
up to 3750
up to 4000
Voltage derating as a function of the installation altitude (500 to 690 V 3 AC)
Installation altitude
above sea level in m
0 to 2000
up to 2250
up to 2500
up to 2750
up to 3000
up to 3250
up to 3500
up to 3750
up to 4000
Rated converter input voltage
380 V
400 V
100 %
100 %
100 %
100 %
100 %
100 %
98 %
100 %
95 %
96 %
92 %
Rated converter input voltage
500 V
525 V
100 %
100 %
100 %
100 %
100 %
100 %
100 %
100 %
420 V
440 V
460 V
100 %
98 %
98 %
94 %
95 %
91 %
97 %
93 %
89 %
93 %
89 %
85 %
91 %
87 %
83 %
87 %
83 %
80 %
575 V
600 V
660 V
100 %
98 %
94 %
91 %
98 %
89 %
98 %
94 %
85 %
94 %
91 %
83 %
91 %
87 %
80 %
S120 Cabinet Modules Equipment Manual
Manual, (GH5), 10/2008, A5E00427098A
480 V
96 %
94 %
90 %
88 %
85 %
82 %
79 %
76 %
690 V
96 %
94 %
90 %
88 %
85 %
82 %
79 %
76 %