Configuration
The Auxiliary Power Supply Module is connected on the plant side to a voltage
corresponding to the respective rated device voltage.
The standard version contains the following components:
● Fuse switch disconnector with fuse monitoring for external evaluation
● Supply of auxiliary busbar system with 3 auxiliary voltages:
● Customer terminal blocks 230 V 1 AC and 380 V 2 AC, e.g. for supplying power to a
● Transformer with output voltage 230 V 1 AC
● SITOP power supply 24 V DC
● 6-pole auxiliary current busbar for 24 V DC supply and fan power supply, including the
● PE busbar, nickel-plated (60 x 10 mm), including jumper for looping through to the next
Note
The configuration example of the Auxiliary Power Supply Module is used to illustrate the
positioning of the factory-fitted components. They show the maximum possible configuration
of the modules, which contain all options that can be ordered.
S120 Cabinet Modules Equipment Manual
Manual, (GH5), 10/2008, A5E00427098A
– 24 V DC for the electronics power supply
– 230 V 1 AC for supply of 230 V AC loads
– 380 to 690 V 2 AC for supply of device fans (corresponding to the respective rated
device voltage)
second auxiliary voltage busbar system (option K75)
jumpers for connecting the Cabinet Modules
Cabinet Module.
Cabinet Modules
5.8 Auxiliary Power Supply Modules
223