5.3

Smart Line Modules

5.3.1

General information

Hazardous voltages are present in certain parts of this equipment during operation of the
cabinet unit.
Only qualified personnel may work on the cabinet.
Such personnel must be thoroughly familiar with all the warnings and maintenance
procedures for the cabinet described in the documentation provided.
The successful and safe operation of this cabinet is dependent on correct transport, proper
storage and installation, as well as careful operation and maintenance.
National safety regulations must be observed.
5.3.2

Description

Note
Refer to the layout diagrams and circuit diagrams provided on the enclosed customer CD for
the arrangement of components and interfaces, and for wiring.
Smart Line Modules are infeed/regenerative feedback units. Like the Basic Line Module,
they supply energy to the connected Motor Modules, but unlike the Basic Line Module, they
can feed back regenerative energy. The infeed occurs over a diode jumper, while stable,
line-commutated regenerative feedback takes place via IGBTs with 100% continuous energy
regeneration.
Under full load, the DC link voltage is higher than the rms value of the rated line voltage by a
factor of 1.30, and under partial load by a factor of 1.32.
Smart Line Modules are suitable for connection to grounded (TN, TT) and non-grounded (IT)
supply systems. The following voltages and power ratings are available:
Line voltage
380 ... 480 V 3 AC
500 ... 690 V 3 AC
The power rating can be increased by connecting Smart Line Modules in parallel.
S120 Cabinet Modules Equipment Manual
Manual, (GH5), 10/2008, A5E00427098A
DANGER
Rated power
250 ... 800 kW
450 ... 1400 kW
Cabinet Modules
5.3 Smart Line Modules
135