Maintenance and servicing
6.4 Replacing components
6.4.5

Replacing power units

The components required for connecting the DC busbars to the power unit are supplied as
standard. If a components is replaced, you may have to restore these connections. The
connection procedure is described in the following section.
Preparatory steps:
● Observe the "five safety rules".
● Disconnect the cabinet from the power supply (do not forget the external power supplies).
● The cabinet units must be installed and secured properly.
● Allow unimpeded access to the DC busbars
240
(if necessary, remove the protective covers).
Figure 6-3
Connection to the DC busbar on the Basic Line Module, Smart Line Module, Active
Line Module, Motor Module (chassis format)
S120 Cabinet Modules Equipment Manual
Manual, (GH5), 10/2008, A5E00427098A