3 SPECIFICATIONS

3.5.22 Control response parameter (buffer memory address 49, 81: Un\G49, Un\G81)

3 - 91
(1) The response level to the PID control set value (SV) change is set.
(a) Slow : Set 0.
Set this level to suppress the overshooting caused by the set value
change.
Note that this will increase the settling time.
(b) Normal : Set 1.
Set this level to obtain intermediate characteristics between "Fast"
and "Slow".
(c) Fast
: Set 2.
Set this level to give a faster response to the set value change.
Note that overshoot increases.
MELSEC-Q
3 - 91