3 SPECIFICATIONS
3 - 46
The following table lists the relationship of Forced output manipulated value
(MV) (buffer memory address: 205, 221), Manipulated value (MV) (buffer
memory address: 13, 14), and analog output value.
Manipulated value (MV)
(buffer memory address:
13, 14)
-50 (-5.0%)
0 (0.0%)
1000 (100.0%)
1050 (105.0%)
While Forced output manipulated value (MV) (buffer memory address: 205,
221) is unchanged, the manipulated value (MV) at the start of forced output
continues to be output.
(c) End of a forced output status
When the value in Forced output command (buffer memory address: 204,
220) is changed to 0 (Forced output not commanded), the value 0 is stored
in Forced output status flag (buffer memory address: 266, 522).
After that, forced output ends and the operation shifts back to the control
before the execution of the forced output function.
Forced output manipulated value
(MV) (buffer memory address:
205, 221)
-200
0
4000
4200
MELSEC-Q
Analog output value
3.2mA
4.0mA
20.0mA
20.8mA