Appendix 2 New Functions Of The Q62Hlc - Mitsubishi Electric MELSEC-Q Series User Manual

Loop control module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

APPENDICES

Appendix 2 New Functions of the Q62HLC

Item
Intelligent function module
switch setting (Switch 2)
Manipulated value (MV)
App.
Appendix - 2
The following describes the new function of the Q62HLC.
(1) Functions added to products with product information (first five
digits) of "10022" or later, or a serial number (first five digits) of
"10011" or later
Existing model
Use prohibited (fixed to 0)
The manipulated value (MV)
becomes -50 for 25ms when
switching to program control.
(Suspends the PID control to switch
into program control.)
Description
Model (product information (first five
digits) of "10022" or later, or serial
number (first five digits) of "10011" or
later)
Control status when switching to
program control can be selected.
1: Switch with executing control
Other than 1: Switch with suspending
control
The control status when switching to
program control can be selected in
the intelligent function module switch
setting (Switch 2).
MELSEC-Q
Reference
Section 4.5
Section
3.2.19
Appendix - 2