Parameter Change In Program Control Function - Mitsubishi Electric MELSEC-Q Series User Manual

Loop control module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

3 SPECIFICATIONS

3.2.18 Parameter change in program control function

CH
1
1
275
276
2
531
532
1
282
286
2
538
542
1
283
287
2
539
543
1
284
288
2
540
544
1
285
289
2
541
545
3 - 49
(1) Parameter change in program control function
Buffer memory settings can be changed and reflected to the control in
execution without stopping program control.
This function is enabled only when the bit 1 of the switch 3 is set to 1 (Enable)
in the intelligent function module switch setting. When the bit 1 of the switch 3 is
0 (Disable), and if a buffer memory setting is changed during program control, a
write data error occurs.
(2) Execution of the parameter change in program control function
When this function is enabled, control data, zone PID data, and pattern data
can be changed during program control. Turning Setting change command
(YnB) from off to on reflects the change to the control.
If a write data error occurs during setting change, the program control proceeds
with the setting before the change.
The buffer memory areas that can be changed are described under (a) to (c).
(a) Control data
Buffer memory address
(decimal)
CH1
CH2
272
528
273
529
274
530
501
757
*1: Regardless of reflection timing of each, turning Setting change command (YnB) from off to
on checks whether each setting is within the setting range.
(b) Zone PID data
Buffer memory address (decimal)
Zone
2
3
4
5
277
278
279
533
534
535
290
294
298
546
550
554
291
295
299
547
551
555
292
296
300
548
552
556
293
297
301
549
553
557
*1: Regardless of reflection timing of each, turning Setting change command (YnB) from off to
on checks whether each setting is within the setting range.
Buffer memory area name
Execution pattern
Start mode
Time scale
Set value at program control
start (SV_PCS) setting
Buffer memory area
6
7
8
280
281
-
Upper limit
536
537
-
302
306
310
Proportional band (P)
setting
558
562
566
303
307
311
Integral time (I)
559
563
567
304
308
312
Derivative time (D)
560
564
568
305
309
313
Control response
parameter
561
565
569
Reflection timing
• When the program pattern being executed is
processed until END
• RESET
RUN
RESET
RUN
Setting change command (YnB) OFF
RESET
RUN
Reflection timing
name
Setting change command
(YnB) OFF
MELSEC-Q
*1
ON
*1
ON
3 - 49