3 SPECIFICATIONS
3.5.68 Program pattern (buffer memory address 320 to 500, 576 to 756: Un\G320 to
Un\G500, Un\G576 to Un\G756)
3 - 111
The program pattern used for the program control function is set.
There are three program patterns and the following eight items (1) to (8) need to be
set.
For the buffer memory addresses of each item, refer to Section 3.5.1.
For details on the program control function, refer to Section 3.2.12.
This setting is available only in the setting mode. However, when the parameter
change in program control function is enabled, this setting can be changed in the
operation mode also. For details on the parameter change in program control
function, refer to Section 3.2.18.
To activate the change, turn on Setting change command (YnB).
(1)
Program pattern final setting
(a) The final segment for the program pattern is set.
At link setting, each program pattern execution will complete at the final
segment.
(b) The default value is 16.
The setting range is 1 to 16.
(2) Program pattern link setting
(a) The Q62HLC can link program patterns and set a program pattern with up to
48 segments. (One program pattern consists of 16 segments.) The pattern
link specifies the program pattern of the link destination.
(b) When the program pattern has been linked, the program pattern of the link
destination is executed in sequential order starting from segment 1. The link
destination program pattern of the segment 1 set value starts from the set
value at the pattern end of the link source.*
source is not performed.
*1: The same operation as the PV starting 1 of Section 3.5.65 "Start mode"
Example: When the program pattern 2 is specified according to the link
setting of the program pattern 1
MELSEC-Q
1
The pattern end output of the link
3 - 111