9 POSITIONING CONTROL
Setting item
Da. 1 Operation pattern
Da. 2 Control method
Da. 3 ACC/DEC time
Da. 4 DEC/STOP time
Da. 5 Command speed
Positioning address/
Da. 6
movement amount
Da. 7 Dwell time
Refer to "Section 4.5 List of positioning data" for the setting details.
9 - 15
Downloaded from
ManualsNet.com
Restrictions
(1) If "Continuous path control" is set in " Da. 1 Operation pattern", the "Continuous
path control not possible" error (error code: 503) occurs, disabling a start.
(2) "Speed-position switching control" cannot be set in " Da. 2 Control method" of
the positioning data if "Continuous path control" is set in " Da. 1 Operation
pattern" of its preceding positioning data. (For example, if the operation pattern
of positioning data No. 1 is "Continuous path control", "Speed-position
switching control" cannot be set in positioning data No. 2.) If such setting has
been made, the "Continuous path control not possible" error (error code: 503)
occurs, resulting in a deceleration stop.
(3) Under speed control of speed-position switching control, the software stroke
limit range is checked only when "1: Update" has been set in " Pr. 4 Current
feed value during speed control".
If the movement amount has exceeded the software stroke limit range during
speed control at the setting of other than "1: Update", the "Software stroke limit
+, -" error (error code: 103 or 104) occurs, resulting in a deceleration stop.
(4) If the setting value of " Da. 6 Positioning address/movement amount" is
negative, the "Setting range outside" (error code: 513) occurs.
(5) If the movement amount of position control set in " Da. 6 Positioning
address/movement amount" is less than the deceleration distance from " Da. 5
Command speed", deceleration processing is started at the input of the speed-
position switching signal.
(6) To suppress the variation of the stopping position after switching to position
control, turn ON the speed-position switching signal in the stable speed region
(constant-speed status).
(7) If "0" has been set in " Pr. 6 Bias speed at start", starting operation at the
setting of "0" in " Da. 5 Command speed" for speed control of speed-position
switching control will result in the following.
• 0 speed (Md. 7 Status: b2) turns ON.
• Though the axis is at a stop, "Md. 4 Axis operation status" is "Speed.Position
Speed" and the BUSY signal remains ON. (Turning ON the axis stop signal
turns OFF the BUSY signal and changes "Md. 4 Axis operation status" to
"Stopped".)
In this case, setting other than "0" in " Cd. 7 New speed value" and "1" in
" Cd. 6 Speed change request" turns OFF 0 speed (Md. 7 Status: b2),
enabling operation to be continued.
Positioning data setting examples
The following table shows setting examples when "speed-position switching control
by forward run" is set in positioning data No. 1 of axis 1.
Setting example
Positioning
termination
Speed.Position
Ctrl. (Forward)
1000ms
1000ms
50000pulse/s Set the speed to be controlled.
10000pulse
500ms
search engine
Setting details
Set "Positioning termination" assuming the next positioning data will not
be executed. ("Continuous path control" cannot be set in "speed-
position switching control".)
Set speed-position switching control by forward run.
Set the acceleration/deceleration time for speed-position switching control.
Set the deceleration stop time for speed-position switching control.
Set the movement amount after the switching to position control.
Set the time from when a stop (pulse output stop) is made under
position control until the positioning complete signal is output.
(The setting value is ignored if a stop is made under speed control.)
MELSEC-Q
9 - 15