13 TROUBLESHOOTING
Related buffer memory address
Axis 1 Axis 2 Axis 3 Axis 4 Axis 5 Axis 6 Axis 7 Axis 8
53
153
253
6
106
206
7
107
207
Pr. 6 Bias speed at start
8
108
208
9
109
209
55
155
255
Refer to "Section 4.5 List of positioning data".
13 - 12
Downloaded from
ManualsNet.com
353
453
553
653
Pr. 5 Speed limit value
306
406
506
606
307
407
507
607
308
408
508
608
309
409
509
609
355
455
555
655
search engine
Setting range
Cd. 4 Restart request
753
1: Make restart
1 to 200000 (pulse/s)
706
707
0 to 200000 (pulse/s)
708
709
Cd. 6 Speed change request
755
1: Make speed change
Da. 1 Operation pattern
0: Positioning termination
1: Continuous positioning control
2: Continuous path control
Da. 6 Positioning address/movement
amount
-2147483648 to 2147483647 (pulse)
(For position control)
MELSEC-Q
Remedy
Normalize the start request ON timing.
• Do not make a restart request in
" Md. 4 Axis operation status" of other
than "Stopped".
• Do not make a restart request during
OPR control or JOG operation.
Change the set speed or " Cd. 7 New
speed value" to not less than " Pr. 6 Bias
speed at start" and to not more than
" Pr. 5 Speed limit value".
Do not make a speed change during
position control or during OPR control.
Correct " Da. 6 Positioning
address/movement amount" or change
" Da. 1 Operation pattern" to "Positioning
termination".
(Refer to Section 9.1.2.)