NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual (1350 mm Depth)
Tab
Issue 04 (2022-12-15)
Parameter
Smart diagnosis
function
Password required for
start or shutdown
onsite
Altitude
Liquid pipe length
Height difference
between indoor and
outdoor units
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Power-On Commissioning
Description
● Enable: If there is an intelligent
temperature control monitoring
board, this function is enabled to
start refrigerant status detection.
● Disable: The smart diagnosis
function is disabled.
Conditions for starting refrigerant
status detection:
● No low temperature component is
configured.
● Altitude: ≤ 2000 m
● 7.5 m ≤ equivalent pipe length of
the one-way pipe ≤ 100 m
● –8 m ≤ vertical distance between
the indoor and outdoor units ≤ +30
m
● 5°C ≤ outdoor ambient temperature
≤ 40.5°C
● No: No password is required for
startup or shutdown.
● Yes: A password is required for
startup and shutdown.
Set this parameter based on the actual
altitude.
Set this parameter after Smart
diagnosis function is set to Enable.
Specify the length of the liquid pipe
between the indoor and outdoor units
of a smart cooling product.
Set this parameter after Smart
diagnosis function is set to Enable.
Specify the height difference between
the indoor and outdoor units of a
smart cooling product.