Startup - Huawei NetCol5000-A050 User Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual (1350 mm Depth)
Parameter
Enable WiFi
WiFi group sharing
enable
Step 3 Tap Submit.
----End

6.6 Startup

Context
On the home screen of the display module, there are Start and Shutdown
buttons for controlling the startup and shutdown of the unit.
Initial Startup
After factory settings are restored, startup verification is required.
Step 1 Tap Start on the home screen to enter the initial startup screen. Tap OK to enter
the startup authorization screen.
Issue 04 (2022-12-15)
If the unit is powered on again after a power failure, the unit automatically
restores to the original startup/shutdown state before the power failure.
Hardware ports are reserved on the display module to control the status of
remote dry contacts or remote startup and shutdown signals. The status of
remote dry contacts and remote startup and shutdown signals is started by
default.
A unit can be started over the screen or NMS only when the status of remote
dry contacts or remote start/shutdown signal is Start.
If you choose Settings > System Settings > System Control and set
Password required for start or shutdown onsite to Yes, a password is
required for startup or shutdown. If you set Password required for start or
shutdown onsite to No, no password is required for startup or shutdown.
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
Enables the WiFi function of the smart cooling product.
The default status is Disable.
When a mobile phone is connected to the WiFi of the
smart cooling product, it can access the units in the
same FE cascading network.
6 Power-On Commissioning
133

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-a050h4we2Netcol5000- a050h40e2

Table of Contents