NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual (1350 mm Depth)
4.1.3 Indoor Unit Installation Position
Precautions
●
●
●
Issue 04 (2022-12-15)
Figure 4-1 Top pipe routing
(1) Inverted U-shaped
(2) Oil trap
trap
Figure 4-2 Bottom pipe routing
(1) Inverted U-shaped
(2) Oil trap
trap
If the actual total load of servers corresponding to a single smart cooling
product is less than 10% of the rated cooling capacity of the smart cooling
product or the equipment room is not properly sealed, the humidity in the
equipment room may be too high. This is not a product quality issue and
should be dealt with by adding a dehumidifier.
Do not install smart cooling products near noise-sensitive places such as
offices and meeting rooms.
Before installation, check whether the installation environment meets the
requirements and whether the building needs to be altered to facilitate pipe
layout, cable routing, and ventilation duct construction.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 System Installation
(3) Tilted gas pipe
(4) Tilted liquid pipe
(3) Tilted gas pipe
(4) Tilted liquid pipe
47