Huawei NetCol5000-A050 User Manual page 46

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual (1350 mm Depth)
Figure 3-2 Hole dimensions
Item
Power system
Power supply
Maximum current
Operating temperature
Operating humidity
Storage temperature
Storage humidity
Maximum operating
altitude
IP rating
Refrigerant
Cooling capacity
Air supply mode
Air volume
Issue 04 (2022-12-15)
Copyright © Huawei Digital Power Technologies Co., Ltd.
NetCol5000-
A050H4WE2
380–415 V AC, 50/60 Hz, 3PH+N+PE
Tolerance: rated voltage –10% to +10%; rated
frequency –3 Hz to +3 Hz
Dual power supplies
46 A
18–45°C
20%–80% RH
–40°C to +70°C
5%–95% RH (non-condensing)
4000 m
IP20
R410A
45 kW
Tested under rated working conditions (indoor dry-
bulb temperature: 37°C, relative humidity: 20%,
outdoor temperature: 35°C).
Horizontal flow
3
9000 m
/h
3 Technical Specifications
NetCol5000-A050H40E2
40 A
36

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-a050h4we2Netcol5000- a050h40e2

Table of Contents