Huawei NetCol5000-A050 User Manual page 60

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual (1350 mm Depth)
Space Requirements
The outdoor unit can be installed horizontally, vertically, or compactly.
● If the outdoor unit is installed compactly, the cooling capacity of the indoor
unit will decrease. Therefore, exercise caution when performing this operation.
● When the outdoor unit is horizontally installed, the outdoor unit and low
temperature component must be placed on bases or concrete bases of the
same height. When the outdoor unit is vertically installed, the outdoor unit can
be 1.5 m higher than the low temperature component at most and cannot be
lower than the low temperature component.
● When the outdoor unit is vertically installed, do not place the low temperature
component at the air outlet.
● The dotted line boxes in the figures indicate the optional low temperature
component.
Figure 4-5 Space requirements for horizontal installation
Figure 4-6 Space requirements for vertical installation
Issue 04 (2022-12-15)
Direct sunlight: In high-temperature areas, avoid exposing the outdoor unit to
direct sunlight.
Wind and sand: Prevent sand from entering the condenser in deserts and
windy and sandy areas.
Catkins season: Prevent catkins from entering the condenser and clean up
catkins at the air intake and exhaust vents.
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 System Installation
50