Step 3 Install the new wet film humidifier and connect the water inlet pipe.
Step 4 Open the front-end water valve.
Step 5 Install the air filter and close the rear door.
Step 6 After startup, choose Maintenance > Performance Maintenance on the home
screen to access the performance maintenance screen, and clear the runtime of
the humidifier.
Step 7 Check that the smart cooling product is running properly and no alarm is
generated.
----End

11.5 Replacing a Condensate Pump

Prerequisites
Before replacing the condensate pump, drain water from the water pan
completely.
Procedure
Step 1 Open the rear door and remove the air filter.
Step 2 Tap Shutdown on the home screen of the display module, and turn off the active
power switch QF1 and standby power switch QF2.
Exercise caution because the device is still energized after it is shut down on the
home screen of the display module.
Step 3 Remove the condensate pump.
1.
2.
3.
Issue 04 (2022-12-15)
A condensate pump needs to be replaced.
A spare condensate pump of the same model is available and functional.
Tools: flat-head screwdriver, Phillips screwdriver
NO TICE
NO TICE
Open the front door and remove the cover from the condensate pump.
Cut off the cable tie of the condensate pump cable and remove the
interconnection terminal.
Remove the hose clamps from the drain outlet of the water pan and the
outlet of the check valve, and remove the hoses. Remove the screws that
secure the condensate pump assembly, and pull out the condensate pump
assembly.