4.4.3 Securing the Cabinet

Step 1 Determine the installation position.
Step 2 Drill mounting holes using a hammer drill.
Step 3 Push the cabinet to the installation position.
Step 4 Level the cabinet using an adjustable wrench.
● Do not remove anchor bolts. Otherwise, you need to rework them for use.
● Anchor bolt adjustment method: Wrench an anchor bolt clockwise to elevate a
cabinet, or wrench an anchor bolt anticlockwise to lower it. The anchor bolts
can be adjusted within a range of 0–8 mm.
● Levelness check standard: Ensure that the cabinet is level in width and depth
directions when leveling the cabinet. Put a level at the bottom of the cabinet in
width and depth directions and check that the air bubble is in the middle
between the two lines marked on the glass tube.
Issue 04 (2022-12-15)
NO TE
This section describes how to install the cabinet on the concrete floor.