NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual (1350 mm Depth)
Parameter
Number of running
systems in this group
Percentage of units
allowed to dehumidify
in this group
Rotation function
Rotation period
Rotation time
Forced rotation
Issue 04 (2022-12-15)
Description
Specifies the number of running units in this group. The
value is an integer ranging from 1 to the value of
Number of systems in this group.
NOTE
Set Percentage of units allowed to dehumidify in
this group based on site requirements.
NOTE
The number of units that perform the dehumidification
function is controlled to prevent all units in the group
from starting dehumidification at the same time,
thereby avoiding supercooling and temperature
fluctuation in the equipment room.
● Number of units allowed to dehumidify is the
● If the anti-competitive running mode of the
Indicates whether to allow the smart cooling products
to work as the standby device in turn, maximizing their
service life.
NOTE
Number of days for rotation (1–30).
Specifies the start time of rotation for the active and
standby units. 24 time points in a day (0–23).
Indicates whether to enable forced rotation regardless
of the specified rotation time. After a forced rotation,
the rotation period starts again.
Copyright © Huawei Digital Power Technologies Co., Ltd.
This parameter is displayed after Teamwork function is set to
Enable.
You are advised to retain the default value.
roundup value of Total number of systems in this
group multiplied by Percentage of units allowed
to dehumidify in this group. The units allowed to
dehumidify are automatically deployed among all
running units.
teamwork group is dehumidification, the master
unit sends the anti-competitive running flag whose
value is dehumidification allowed to the units
allowed to dehumidify.
It is recommended that the function be enabled when the
load is even.