Huawei NetCol8000-A013 User Manual page 102

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
Alarm
Alarm Name
ID
211
OutUnit Input
Overcur Alarm
212
Comp Drive
Overload Alarm
213
Comp Start Fail
Alarm
Issue 04 (2022-11-25)
System
Action
The
compressor
shuts down.
The
compressor
shuts down.
The
compressor
shuts down.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 System Operation and Maintenance
Possible Causes
1. The condenser fins
are dirty or blocked.
2. The outdoor unit is
not properly
installed.
3. The outdoor
temperature sensor
displays an incorrect
temperature or is
faulty.
4. The input voltage of
the unit fluctuates.
1. The refrigerant is
liquefied or the
compressor startup
resistance is high.
As a result, the
compressor fails to
start.
2. At least two cables
between the
compressor and the
drive board are not
connected.
3. The output of the
inverter module of
the compressor
drive board is faulty.
The difference between
the compressor control
output rotational
speed and the actual
compressor rotational
speed is greater than
the control threshold.
Solution
1. Clean the condenser
fins.
2. Reinstall the
outdoor unit.
3. Adjust or replace
the outdoor
temperature sensor.
4. Stabilize the input
voltage.
1. Check the
refrigerant of the
compressor.
2. Check the cables
between the
compressor and the
drive board.
3. Replace the
compressor drive
board.
1. Check the
compressor status.
2. Refill refrigerant.
3. Replace the
compressor drive
board or
compressor.
95