NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
Multiple Outdoor Units
When multiple outdoor units are to be installed, if they cannot be installed against
a wall or the local outdoor temperature may be below –5°C, place an air baffle at
the air intake side of each outdoor unit.
Figure 3-11 Space requirements for installing multiple outdoor units

3.4 Layout Principles

The layout principles are as follows:
Issue 04 (2022-11-25)
Figure 3-10 Requirements for installing an outdoor unit on a wall
NO TE
● Ensure that the bearing capacity of the support platform is greater than 230 kg.
● Reserve a clearance of at least 300 mm from the left or right side of the outdoor
fan for maintenance personnel to walk through.
● The grid structure is recommended to avoid the air exhaust and intake of the
smart cooling product being affected by a guardrail structure.
● The figures are only for reference, which can be modified based on the actual site
conditions.
If the outdoor unit is placed higher than the indoor unit, the maximum height
deviation between them should be less than or equal to 20 meters. Install an
oil trap every 5–6 meters in the vertical direction along the gas pipe.
If the indoor unit is placed higher than the outdoor unit, the maximum height
deviation between them should be less than or equal to 5 meters.