Huawei NetCol8000-A013 User Manual page 84

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
Setting
Item
Rotation
Function
Rotation
Type
Rotation
Cycle
Rotation
Time
High
Temp
Start All
Temp for
HT Start
All
Low Temp
Start All
Temp for
LT Start
All
Issue 04 (2022-11-25)
Description
Indicates whether to
disable or enable
the active and
standby smart
cooling products to
work alternatively to
maximize their
service life.
Can be set to
Address or hour
Indicates the interval
between rotations.
The value ranges
from 1 to 30.
Indicates the time
when rotation takes
place. The value can
be any hour in a day
(0–23).
When it is enabled,
if the return air
temperature is
higher than Temp
for HT Start All, all
the smart cooling
products in a group
will start cooling
simultaneously.
-
When it is enabled,
if the return air
temperature is
higher than Low
Temp Start All, all
the smart cooling
products in a group
will start heating
simultaneously.
-
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Power-On Commissioning
Setting Principle
It is recommended
that the function be
enabled when the
load power is even.
You are advised not
to change the value.
/
/
You are advised not
to change the value.
You are advised not
to change the value.
You are advised not
to change the value.
You are advised not
to change the value.
Default Value
Disable
Address
1D
00:00
Disable
31°C
Disable
13°C
77