Huawei NetCol8000-A013 User Manual page 99

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
Alarm
Alarm Name
ID
205
Comp HP Switch
Alarm
206
Comp HP Switch
Lock Alarm
Issue 04 (2022-11-25)
System
Action
The
compressor
shuts down.
The
compressor
shuts down.
(The alarm
needs to be
manually
cleared.)
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 System Operation and Maintenance
Possible Causes
1. The condenser fins
are dirty or blocked.
2. The outdoor fan or
its drive is faulty.
3. The cables to the
high pressure switch
are loose or
damaged.
4. The high pressure
switch is faulty.
5. The refrigerant is
overfilled.
6. The outdoor unit is
not properly
installed.
The Comp HP Switch
Alarm is triggered
multiple times within a
specified period of
time.
Solution
1. Clean the condenser
fins.
2. Maintain or replace
the outdoor fan
drive or outdoor
fan.
3. Check the cable
connections to the
high pressure
switch.
4. Maintain or replace
the high pressure
switch.
5. Decrease certain
amount of
refrigerant.
6. Reinstall the
outdoor unit.
Refer to the solution to
the Comp HP Switch
Alarm.
92