3.2.1 Refrigerant R410A

Do not use low-quality refrigerant. The supplier is not responsible for any device
damage caused by low-quality refrigerant.
Follow these suggestions to choose high-quality refrigerant:
1.
2.
Figure 3-1 Checking refrigerant
Table 3-3 Mapping between temperatures and R410A saturation pressures
Temperatur
e (°C)
0
1
2
3
4
5
6
Issue 04 (2022-11-25)
CA UTION
Contact the refrigerant producer to confirm the refrigerant authenticity.
As shown in
Figure
3-1, place the refrigerant in an indoor place with constant
temperature and humidity for 24 hours. Then, use a thermometer to measure
the temperature of the refrigerant tank outer surface and connect a pressure
gauge to the pressure tank to measure the internal pressure. Find the
saturation pressure corresponding to the measured outer surface temperature
from
Table
3-3. If the deviation between the saturation pressure and the
measured internal pressure is greater than 0.2 MPa, the refrigerant does not
meet the requirements and needs to be replaced.
Saturation
Pressure –
Gauge
Pressure
(MPa)
0.7
0.73
0.75
0.78
0.81
0.84
0.87
Copyright © Huawei Digital Power Technologies Co., Ltd.
Temperatu
Saturation
re (°C)
Pressure –
Gauge
Pressure
(MPa)
19
1.31
20
1.35
21
1.39
22
1.43
23
1.47
24
1.51
25
1.56
3 System Installation
Temperatu
Saturatio
re (°C)
n
Pressure –
Gauge
Pressure
(MPa)
38
2.21
39
2.27
40
2.33
41
2.39
42
2.45
43
2.51
44
2.57
34