Huawei NetCol8000-A013 User Manual page 133

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
2.
3.
----End
Issue 04 (2022-11-25)
Table 5-7 Running parameters
Outdoor
Normal
Ambient
Discharge
Temperatur
Pressure
e
Range
Below 15°C
1.5–2.5 MPa
15–35°C
1.5–3.1 MPa
35–45°C
2.5–3.8 MPa
Above 45°C
3.1–4.15
MPa
NO TE
If the suction pressure, discharge pressure, and suction overheating degree is without
normal ranges, check and make sure that:
1. Charge refrigerant in an amount exactly as standard charge required. (Refrigerant
charging too much would result in high discharge pressure. Refrigerant charging too
little would result in low suction pressure, low discharge pressure, and high suction
overheating degree.)
2. The air inlet and outlet of outdoor unit are without block. (The air inlet and outlet
blockage would result in high discharge pressure.)
On the diagnostic mode screen, change the compressor input to 0 rpm.
Exit the diagnostic mode.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 System Operation and Maintenance
Normal
Reasonable
Suction
Suction
Pressure
Superheat
Range
Degree
0.7–1.2 MPa
4–10°C
Supercool
3–5°C
126