Huawei NetCol8000-A013 User Manual page 82

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
Figure 4-7 Teamwork setting
If the teamwork function is enabled and the unit address is set to 1 (master unit), the menus on
the last two screens are viewable and configurable. Otherwise, the last two screens are not
displayed.
Step 3 Set Teamwork Function to Enable.
Step 4 Set the Unit Address of the master unit to 1 and the Unit Address of the slave
unit to an integer other than 1.
Step 5 Set other parameters based on the following table.
Table 4-4 Teamwork setting
Setting
Item
Teamwork
Function
Issue 04 (2022-11-25)
NO TE
Description
Indicates whether to
disable or enable
the teamwork
function. If the
function is disabled,
a unit operates
independently. If the
function is enabled,
a unit operates in a
team with other
units.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Power-On Commissioning
Setting Principle
Set this parameter
based on onsite heat
load distribution.
Default Value
Disable
75