Huawei NetCol5000-A050 User Manual page 118

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Figure 4-70 Bottom pipe routing
Step 2 Install the water pipe conversion adapter and seal it with sealant, as shown by (2)
in
Figure
Step 3 Cut a cross in the rubber ring using a utility knife and route the pipe wrapped with
the thermal insulation tube through the hole.
Ensure that the rubber ring is not disconnected. If the rubber ring is disconnected
or damaged, seal the gaps around the pipes with mastic cement or thermal
insulation foam.
Step 4 Route the straight-through pipe through the pipe hole at the bottom of the
cabinet and connect the pipe to the PPR pipe using a hot melt gun, as shown by
(3) in
Step 5 Connect the drainpipe to the external drainage system.
Step 6 Wrap thermal insulation foam around the drainpipe (including the connectors).
----End
Top Pipe Routing
When routing pipes from the top, do not route the pipes over servers or other
devices to protect them from being affected by pipe leaks.
Step 1 Remove the drainpipe plug, as shown in
Issue 13 (2023-08-20)
4-70.
NO TICE
Figure
4-70.
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
Figure
4-71.
4 Installation
107

Advertisement

Table of Contents
loading

Table of Contents