6.5.3.4 Setting Communications Parameters (SNMP Protocol)

Context
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > SNMP Settings.
Figure 6-16 Setting SNMP communications parameters
Step 2 Set SNMP Version based on site requirements, and then tap Submit.
Issue 13 (2023-08-20)
To set communications parameters, log in as the admin user.
This section is suitable only for SNMP. Skip this section if you use Modbus.
Record the values entered in this section. They will be used when you connect
a unit to a network management system (NMS).
One unit supports concurrent access of up to 6 NMSs through SNMP.
When SNMP Version is set to ALL or SNMPv1&v2c, you can set Read
Community and Write Community.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
This parameter is configurable when Link mode
involves Client.
● Connecting to the NetEco: Set this parameter to
32907 if Client encryption is enabled, or set it to
32906 if Client encryption is disabled.
● Connecting to other NMSs: You are advised not to
change the value. In special cases, set this
parameter based on the site requirements.
Secondary authentication password used for Modbus-
TCP connection.
6 Power-On Commissioning
166