How To Commission Single Component - Huawei NetCol5000-A050 User Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual

12.3.15 How to Commission Single Component

Context
Procedure
Step 1 Choose Maint > Diagnostic Mode > Enter.
Step 2 Set Indoor fan to 50%.
For safe system operation, when smart cooling product components are turned on,
the following coupling relationships are presented:
● When the electric heater is turned on, the indoor fans will turn on
automatically.
● When the electrode humidifier is turned on, the indoor fans and inlet water
solenoid valve will start automatically.
● When the input value of the indoor fan is less than the minimum speed, the
indoor fan will run at the minimum speed.
Step 3 Check that the indoor fans run properly, and no alarm generates.
Step 4 Choose Maint > Diagnostic Mode > Exit or tap
----End
Issue 13 (2023-08-20)
On the diagnostic mode screen, you can turn on or off components, and
control their output ratio.
If you need to manually turn on or off system components in diagnostic
mode, ensure that the smart cooling product is started before operation.
Take commissioning the indoor fan as an example.
NO TE
The screen for entering the diagnostic mode:
● Components are interlocked. Therefore, buttons for turning on or off certain
components are in gray, indicating that operations of the components are not allowed.
● To ensure system security, a component may not promptly respond to operations
performed on this screen. For example, the compressor does not respond promptly after
the Off (On) button is tapped if the shortest running (shutdown) time is not met.
● To exit the diagnostic mode, tap
● The system automatically exits diagnostic mode when it reaches the maximum
diagnostic mode duration.
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
on the status bar.
to exit the diagnostic mode.
12 FAQ
258

Advertisement

Table of Contents
loading

Table of Contents