Item
Storage humidity
IP rating
Altitude
Table 3-4 Application environment
Type
Class A (controlled
environment)
Class B (uncontrolled
environment)
Class C (harsh environment)
Class D (marine environment)
Issue 13 (2023-08-20)
NetCol500-A060
5%–95% RH (non-condensing)
IPX5
0–4000 m. If the altitude exceeds 1000 m, the cooling
performance is derated. For details about derating data,
contact technical support.
Copyright © Huawei Digital Power Technologies Co., Ltd.
NetCol500-A080
Description
Indoor environments where the temperature
and humidity are controlled, including rooms
where human beings live
Indoor environment where the ambient
temperature and humidity are not controlled
or outdoor environments (with simple
shielding measures) where the humidity can
reach 100%.
Sea environments or outdoor land
environments (with simple shielding measures)
near pollution sources. Pollution sources refer
to the following areas:
● Areas within 3.7 km away from saline water
areas such as the ocean and saline lakes
● Areas within 3 km of serious pollution
sources, such as metallurgic plants, coal
mines, and heat and power plants
● Areas within 2 km away from medium
pollution sources, such as chemical
factories, rubber plants, and electroplating
factories
● Areas within 1 km away from light pollution
sources, such as food factories, tanneries,
and heating boilers
Areas within 500 m away from the seashore.
3 Technical Specifications