Item
Maximum
operating
temperature on the
refrigerant side
Maximum
operating
temperature on the
cooling water side
Water flow rate
Water-side pressure
bearing
Refrigerant-side
pressure bearing
IP rating
Altitude
Environment
Net weight
Issue 13 (2023-08-20)
Technical Specifications
125°C
60°C
9.5 m
1.2 MPa
4.35 MPa
IP21
0–4000 m (derated when the altitude is greater than 1000
m)
Enclosed indoor environment in which the temperature
and humidity can be controlled within the ranges of 4°C
to 45°C and 5% RH to 90% RH respectively. If the indoor
installation position is ventilated, it should be more than
3.7 km away from the sea or pollution sources (such as
salt lakes, chemical plants, mineral plants, thermal power
plants, and coal mines).
63 kg
Copyright © Huawei Digital Power Technologies Co., Ltd.
3
/h
3 Technical Specifications
39