NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Step 2 Clean the engineering pipes before connecting the water inlet pipe to the engineer
pipe to avoid impurities entering into the humidifier.
Step 3 Connect the water inlet pipe to the engineering pipe and wrap the pipe with
thermal insulation foam.
----End
Top Pipe Routing
When routing pipes from the top, do not route the pipes over servers or other
devices to protect them from being affected by pipe leaks.
Step 1 Straighten the water inlet pipe delivered with the smart cooling product, and route
it from the inside to the outside through the water inlet hole on the top of the
smart cooling product.
Figure 4-73 Top routing of the water inlet pipe
Step 2 Clean the engineering pipes before connecting the water inlet pipe to the engineer
pipe to avoid impurities entering into the humidifier.
Issue 13 (2023-08-20)
NO TE
The other end is a reserved G 1/2 inch connector with inner screw threads. Connect the
other end to a hose or rigid pipe based on site requirements.
NO TICE
NO TE
● The other end is a reserved G 1/2 inch connector with inner screw threads. Connect the
other end to a hose or rigid pipe based on site requirements.
● Secure the water inlet pipe inside the cabinet to the left post of the cabinet using cable
ties.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation
109