Huawei NetCol5000-A050 User Manual page 158

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Tab
Issue 13 (2023-08-20)
Parameter
Height difference
between indoor and
outdoor units
Heating function
Heating mode
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Power-On Commissioning
Description
Set this parameter after Smart
diagnosis function is set to Enable.
Specify the height difference between
the indoor and outdoor units of a smart
cooling product.
● Enable: The device starts heating
when the ambient temperature is
lower than the temperature setpoint
by a certain range.
● Enabled when active power supply is
working: The device starts heating
only when the active power supply is
used and the ambient temperature is
lower than the temperature setpoint
by a certain range. (The electric
heater is an auxiliary function. By
default, it is enabled when the active
power supply is used and is disabled
when the standby power supply is
used.)
● Disable: The heating function is
disabled.
This parameter can be set to
Dehumidifying heating, Low-
temperature heating, or
Dehumidification & Low temperature
heating.
● Dehumidifying heating: When the
dehumidifying function is enabled,
the electric heater is started to
supplement the cooling capacity to
achieve dehumidification at constant
temperature.
● Low-temperature heating: The
heating function is enabled when the
current temperature is lower than the
temperature setpoint by a certain
value.
● Dehumidification & Low temperature
heating: Both functions are available.