Physical Ports - Huawei NetCol5000-A050 User Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
The low temperature component automatically controls the condensing pressure
to ensure that the smart cooling product works safely and reliably at an outdoor
ambient temperature of –40°C.
Figure 2-10 Low temperature component
(1) Safety valve
(4) Condensing pressure
regulator valve
(7) Port for the indoor unit gas
pipe

2.2.7 Physical Ports

Table 2-5 Physical ports
Item
Indoor unit
Issue 13 (2023-08-20)
When the outdoor condensing pressure is lower than the designed opening
pressure of the condensing pressure regulator valve, the regulator valve closes
and the differential pressure valve opens. The refrigerant at the compressor
outlet is bypassed to the liquid storage unit of the low temperature
component through the differential pressure valve, ensuring that the
condensing pressure stays within a safe and reliable operating range.
When the condensing pressure is higher than the designed opening pressure
of the condensing pressure regulator valve, the regulator valve opens and the
differential pressure valve closes. The refrigerant at the compressor outlet
flows to the liquid storage unit of the low temperature component through
the condenser, and the system runs properly.
Refrigerant liquid
pipe
Refrigerant gas pipe
Copyright © Huawei Digital Power Technologies Co., Ltd.
(2) Port for the indoor unit
liquid pipe
(5) Differential pressure valve
Specifications
Outer diameter of 5/8 inch (15.88 mm),
welding
Outer diameter of 7/8 inch (22.22 mm),
welding
2 Product Description
(3) Port for the outdoor unit
liquid pipe
(6) Port for the outdoor unit
gas pipe
31