Huawei NetCol5000-A050 User Manual page 157

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Tab
Issue 13 (2023-08-20)
Parameter
Temp control
intelligent monitoring
board
Smart diagnosis
function
Password required for
start or shutdown
onsite
Altitude
Liquid pipe length
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Power-On Commissioning
Description
A temperature control intelligent
monitoring board is used to monitor the
outdoor environment.
Check the interior of the electric control
box of the outdoor unit:
● If there is an intelligent temperature
control monitoring board, set this
parameter to Yes.
● If there is no intelligent temperature
control monitoring board, set this
parameter to No.
● Enable: If there is an intelligent
temperature control monitoring
board, this function is enabled to
start refrigerant status detection.
● Disable: The smart diagnosis function
is disabled.
Conditions for starting refrigerant status
detection:
● No low temperature component is
configured.
● Altitude: ≤ 2000 m
● 7.5 m ≤ equivalent pipe length of the
one-way pipe ≤ 100 m
● –8 m ≤ vertical distance between the
indoor and outdoor units ≤ +30 m
● 5°C ≤ outdoor ambient temperature
≤ 40.5°C
● No: No password is required for
startup or shutdown.
● Yes: A password is required for
startup and shutdown.
Set this parameter based on the actual
altitude.
Set this parameter after Smart
diagnosis function is set to Enable.
Specify the length of the liquid pipe
between the indoor and outdoor units
of a smart cooling product.
146