Temperature Setpoint
(°C)
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
----End
Issue 13 (2023-08-20)
Copyright © Huawei Digital Power Technologies Co., Ltd.
Lower Limit of
Humidity Setpoint (%
RH)
16.9
15.9
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
6 Power-On Commissioning
Upper Limit of
Humidity Setpoint (%
RH)
80
80
80
75.3
70.9
66.9
63
59.5
56.1
53
50
47.3
44.7
42.2
40
37.8
35.8
33.9
32.1
30.5
28.9
27.4
26
24.7
23.4