Replacing A Wet Film Humidifier - Huawei NetCol5000-A050 User Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Figure 11-38 Installing a condensate pump
Step 6 Power on the device, choose Maint > Performance Maint on the home screen of
the display module to access the performance maintenance screen, and clear the
total runtime of the condensate pump.
Step 7 Tap Startup on the home screen. Ensure that the smart cooling product is running
normally without any alarms.
----End

11.12 Replacing a Wet Film Humidifier

Prerequisites
Context
The wet film humidifier needs to be maintained from the rear door.
Procedure
Step 1 Tap Shutdown on the home screen of the display module.
Exercise caution because the device is still energized after it is shut down on the
home screen of the display module.
Issue 13 (2023-08-20)
A wet film humidifier needs to be replaced.
A spare wet film humidifier of the same model is available and functional.
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
11 Parts Replacement
230

Advertisement

Table of Contents
loading

Table of Contents