Setting Communications Parameters (Modbus-Tcp Protocol) - Huawei NetCol5000-A050 User Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Step 2 Set the baud rate, communication address, and RS485 monitoring group.
Parameter
Baud rate
Communication address
RS485 monitoring grouping
----End

6.5.3.3 Setting Communications Parameters (Modbus-TCP Protocol)

Context
This section applies to the scenario where the unit is connected to the NMS.
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > WAN IP Settings, and
set the IP address, subnet mask, and gateway based on the actual plan.
Figure 6-15 WAN IP Settings
Issue 13 (2023-08-20)
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
Set this parameter based on the baud rate of the
connected device. The baud rate must be the
same as that on the NMS. The value can be 9600
or 19200.
Enter the communications address of the smart
cooling product as planned. The NMS
communicates with the smart cooling product
using this address, and the communications
addresses of two smart cooling products
connected to the same NMS must be different.
● In non-grouping scenarios, set RS485
monitoring grouping to Enable for each unit.
● In grouping scenarios, set RS485 monitoring
grouping to Enable for the unit with the
COM/FE port connected, and Disable for
other units.
6 Power-On Commissioning
164

Advertisement

Table of Contents
loading

Table of Contents