Initialization Function - Mitsubishi Electric MELSEC iQ-R Series User Manual

High speed data logger module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

1.15

Initialization Function

The initialization function initializes a firmware update-prohibited password retained in a high speed data logger module.
Operating procedure
1.
Select "Module Initialization Setting" in "Basic Settings"  "Various Operations Settings"  "Mode Settings" for a high
speed data logger module in an engineering tool. (Page 237 Basic Settings)
2.
Set the CPU module to the STOP state, and write the parameters.
3.
Reset the CPU module.
After the CPU module is reset, a firmware update-prohibited password is initialized automatically. The LED display for
the initialization is as follows:
Status
Initialization completed
4.
When the initialization is completed normally, return the mode setting changed in step 1 to "Online" and reset the CPU
module.
5.
When the initialization is completed abnormally, check if measures are taken to reduce noise of the programmable
controller system, and perform the initialization again. If it is completed abnormally again, a hardware failure may occur
in a high speed data logger module. Please contact your local Mitsubishi Electric sales office or representative.
Do not use an electric screwdriver when removing the module. Loose the module fixing screws completely to remove the
module.
1 FUNCTION
106
1.15 Initialization Function
Normal completion
Abnormal completion
RUN LED status
ON
ON
ERR LED status
OFF
ON