■[Co-existence network route] tab
Item
Intervening system
Module type
Module setting
Access target system
Module type
Module setting
■[Multiple CPU specification] tab
Item
Multiple CPU specification
■[Response monitoring time] tab
Item
Timeout time
*1 If the general sampling delay occurs, the response timeout error occurrence may be extended by a maximum of the general sampling
delay time.
For details on the general sampling delay time, refer to the following:
Page 315 General sampling delay time area (Un\G800 to 805)
■[Finish] tab
Item
Access target CPU name
[Global label/Common device
comment import setting] button
[Communication test] button
Description
Select the module type on the routed system side.
Head I/O
Set the start I/O number of the module on the routed system side.
Displays the module type on the access target system side.
Network No.
Set the network number of the module on the access target system side.
Station No.
Set the station number of the module on the access target system side.
Description
Select the CPU number when the access target CPU is a multiple CPU system.
Description
Set the timeout time from when the high speed data logger module sends a request to the access target CPU until it
receives a reply.
When there is no response within the set time from the access target CPU, the response timeout error (error code:
*1
1A82H) occurs.
Description
Set the access target CPU name. (Up to 32 characters)
If the access target CPU setting name is duplicated, the suffixes ((1), (2), ...) will be added.
Open the "Global label/Common device comment import setting" screen.
Page 116 "Global label/Common device comment import setting" screen
Conducts a connection test to the CPU module with the configured settings.