Mitsubishi Electric MELSEC iQ-R Series User Manual page 277

High speed data logger module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error code
Error name
1C2AH
Recipe execution operation
error
1C2BH
Incorrect operation type error
1C2DH
Device error
1C2EH
Number of data error
1C2FH
Incorrect device value error
1C30H
Device error
1C31H
Number of blocks error
1C32H
Number of records error
1C33H
Record number error
1C35H
SD memory card access error
1C36H
SD memory card access error
1C37H
SD memory card access error
1C38H
SD memory card access error
1C3AH
Module suspension error
1C3BH
Module suspension error
1C3CH
Module suspension error
1C3DH
Recipe execution operation
error
1C3EH
Record number specification
error
1C3FH
No specified file error
1C40H
Incorrect file name error
1C41H
File size error
1C42H
File size error
1C44H to 1C46H
Recipe file error
1C49H to 1C5AH
Recipe file error
1C5BH
SD memory card access error
Error description
The recipe execution operation is already being
performed.
An incompatible recipe execution operation type
is specified.
An incorrect device is specified.
Number of data out of the range is specified.
Failed to acquire the device value.
An incorrect device is specified.
Incorrect number of blocks is specified.
Incorrect number of records is specified.
An incorrect value is specified for the start value of
record number.
The access to the SD memory card was
attempted when its access state was "Preparing
access".
The access to the SD memory card was
attempted when the file access was being
stopped.
The access to the unformatted SD memory card
was attempted.
The access to the SD memory card was
attempted while it is being formatted.
The recipe execution operation was performed
when the operation of high speed data logger
module was being suspended.
The recipe execution operation was performed
when the module suspended error is being
occurred.
The recipe execution operation is executed while
the settings are being updated.
Or the access to the SD memory card was
attempted while it is being formatted.
The recipe execution operation is already being
performed.
A record number out of the range is specified in
the RCPWRITE instruction.
A file name which does not exist is specified.
A character which cannot be used for a file name
is specified.
A recipe file whose size exceeds 512 KB is
specified.
The size of recipe file has exceeded 512 KB by
writing data.
The recipe file is not correctly formatted.
Or corrupted recipe file is specified.
The recipe file is not correctly formatted.
Or corrupted recipe file is specified.
The access to the SD memory card was
attempted when its access state was "Preparing
access".
Corrective action
• Retry after the recipe execution operation is
completed.
• Correct the control data of the RCPREAD
instruction.
• Check the device of the specified Recipe file.
• Specify 1 for "Number of data" when the data
type is "Bit".
• Specify 1 to 256 for "Number of data" when the
data type is other than "Bit".
• Check the device value.
• Check the records or blocks of the specified
recipe file.
• Check the specified recipe file.
• Check the device of the specified Recipe file.
• Specify a value within the range.
• Specify a value within the range.
• Specify 1 for the start value of record number.
• Access the SD memory card again when the
access state is "Accessible".
• Check if a SD memory card is inserted.
• Execute "Access restart" and retry.
• Turn the clear file access stop request (Y3) ON,
and retry after the file access status (X2) is
turned OFF.
• After formatting the SD memory card, store
recipe files to the SD memory card, and retry.
• After formatting the SD memory card, store
recipe files to the SD memory card, and retry.
• Execute "Restart" of "Module operation" and
retry.
• Execute "Update settings" of "Module
operation" and retry.
• Remove the module suspended error factor,
reset the CPU module, and retry.
• Retry after the operating status of the module is
changed to "In operation".
• After formatting the SD memory card, store
recipe files to the SD memory card, and retry.
• Retry after the recipe execution operation is
completed.
• Correct the control data of the RCPWRITE
instruction.
• Specify the Recipe file exists in the RECIPE
folder.
• Correct the control data of the RCPWRITE
instruction.
• Specify a file whose size is less than 512 KB.
• Correct the setting of the recipe file to be less
than 512 KB.
• After writing data, adjust the number of blocks/
records/data not to exceed 512 KB.
• Check the format of the specified recipe file.
• Check the format of the specified recipe file.
• Access the SD memory card again when the
access state is "Accessible".
4 TROUBLESHOOTING
4.4 Error Code List
4