Smart power control system
Table of Contents

Advertisement

LUNA2000-200KTL-H1 Smart Power Control System
User Manual
Issue 08 (2024-01-23)
If the Smart PCS is installed in public places (such as parking lots, stations,
and factories) other than working and living areas, install a protective net
outside the device and set up a safety warning sign to isolate the device. This
is to avoid personal injury or property loss caused by accidental contact by
non-professionals or other reasons during device operation.
Do not install the Smart PCS in areas containing flammable materials (such
as sulfur, phosphorus, liquefied petroleum gas, marsh gas, flour, and cotton)
to avoid personal injury or property loss caused by fire or other reasons.
Do not install the Smart PCS in areas containing explosives (such as blasting
agents, display shells, fireworks, and firecrackers) to avoid personal injury or
property loss caused by explosion or other reasons.
Do not install the Smart PCS in areas with corrosive substances (such as
sulfuric acid, hydrochloric acid, nitric acid, hydrogen sulfide, and chlorine) to
avoid Smart PCS failure caused by corrosion, which is not covered under the
warranty.
The mounting structure for the Smart PCS must be fireproof. Do not install
the Smart PCS on flammable building materials to avoid personal injury or
property loss caused by fire or other reasons.
The anti-corrosion level of the Smart PCS is C5 Medium. Therefore, the site
must be a class C or better environment but not a class D or E environment.
Do not install the Smart PCS in an easily accessible place, because the voltage
is high and its enclosure and heat sink are hot during device operation. This is
to avoid personal injury or property loss caused by accidental contact by non-
professionals or other reasons during device operation.
The Smart PCS shall be installed in a well-ventilated environment to ensure
good heat dissipation. The Smart PCS provides self-protection in high-
temperature environments. If the Smart PCS is installed in a poorly ventilated
environment, the power of the Smart PCS may decrease as the ambient
temperature increases.
Do not install the equipment in an area with strong vibration, noise, or
electromagnetic interference. The equipment shall be installed in an
environment with a magnetic field strength less than 4 Gauss. If the magnetic
field strength is greater than or equal to 4 Gauss, the equipment may fail to
work properly. If the magnetic field strength is high, for example, in a
smeltery, you are advised to use a gauss meter to measure the magnetic field
strength of the equipment installation position when the smelting equipment
is running normally.
If the Smart PCS is installed in an enclosed environment, a heat dissipation
device or ventilation device shall be installed. The indoor ambient
temperature must not be higher than the outdoor ambient temperature. The
Smart PCS provides self-protection in high-temperature environments. The
power of the Smart PCS may decrease as the ambient temperature increases.
In off-grid scenarios, install the Smart PCS in a place with a sunshade or
install an awning for the Smart PCS in case of high temperature or direct
sunlight.
The Smart PCS shall be installed in a sheltered place to avoid exposure to
direct sunlight or adverse weather conditions (such as snow, rain, and
lightning). The Smart PCS provides self-protection in high-temperature
environments. If the Smart PCS is installed in a place subject to direct
Copyright © Huawei Technologies Co., Ltd.
4 Installation
28

Advertisement

Table of Contents
loading