Connecting A Pe Cable - Huawei LUNA2000-200KTL-H1 User Manual

Smart power control system
Table of Contents

Advertisement

LUNA2000-200KTL-H1 Smart Power Control System
User Manual
Cable
Type
AC power
Three-core (L1, L2, L3) outdoor
cable
cable and M12 OT/DT terminal
(multi-
(L1, L2, L3)
core)
AC power
Single-core outdoor cable and
cable
M12 OT/DT terminal
(single-
core)
Note [1]: The S
value is valid only if the conductors of the PE cable and AC power cable use the
p
same material. If the materials are different, ensure that the conductor cross-sectional area of the
PE cable produces a conductance equivalent to that specified in this table. The specifications of
the PE cable are subject to this table or calculated according to IEC 60364-5-54.

5.3 Connecting a PE Cable

Precautions
● The grounding shall comply with the local electrical safety regulations.
● It is recommended that the Smart PCS be connected to a nearby ground point.
● The ground point in the AC maintenance compartment serves only as the
Procedure
Step 1 Connect the PE cable.
Issue 08 (2024-01-23)
NO TICE
The ground points of all Smart PCSs in the same array need to be connected to
ensure equipotential bonding for PE cables.
equipotential bonding point for the PE point and cannot replace the PE point of
the enclosure.
Copyright © Huawei Technologies Co., Ltd.
Conductor Cross-
Sectional Area
2
70–240 mm
2
70–240 mm
5 Cable Connection
Outer
Source
Diameter
30–65 mm
Prepared
by the
customer
15–35 mm
Prepared
by the
customer
46