Connecting Fe Communications Cables - Huawei LUNA2000-200KTL-H1 User Manual

Smart power control system
Table of Contents

Advertisement

LUNA2000-200KTL-H1 Smart Power Control System
User Manual
Communications Ports
Figure 5-14 Port description
(1) Network port 2 (FE2)

5.8.1 Connecting FE Communications Cables

Figure 5-15 Connecting FE communications cables (to the SmartACU2000D-D-06)
Issue 08 (2024-01-23)
If the SmartACU2000D-D-06 is used, connect the Smart PCSs to the
SmartACU through FE communications cables. Ensure that the two ends are
connected to G2–G7 of the SmartACU (SWITCH02). A maximum of three ring
networks are supported.
If the SmartACU2000D-D-00, SmartACU2000D-D-01, or SmartACU2000D-
D-03 is used, connect the Smart PCSs to the SmartModule through FE
communications cables. Ensure that the two ends are connected to GE2 and
GE3 of the SmartModule. A maximum of one ring network is supported.
NO TE
The SmartACU2000D-D-00 and SmartACU2000D-D-01 can be configured with the
SmartModule optionally. The SmartACU2000D-D-03 is configured with the
SmartModule by default.
Copyright © Huawei Technologies Co., Ltd.
(2) Network port 1 (FE1)
5 Cable Connection
(3) Communications port
(COM)