SmartLogger2000-(10-C, 11-C)
User Manual
Grid Parameters
Table 7-5 Parameter description
No.
Parameter
1
Grid code
2
Output
mode
3
PQ mode
4
Auto start
upon grid
recovery
5
On-grid
recovery
time
6
Grid
reconnectio
n voltage
upper limit
Issue Draft A (2017-02-15)
Description
Set this parameter
based on the grid code
of the country or
region where the
SUN2000 is used and
the SUN2000
application scenario.
Specifies whether the
SUN2000 has an
output neutral wire
based on the
SUN2000 application
scenario.
If PQ mode 1 is
selected, the
maximum AC output
power equals the
maximum apparent
power. If PQ mode 2
is selected, the
maximum AC output
power equals the rated
output power.
Specifies whether to
allow the SUN2000 to
automatically start
after the power grid
recovers.
Specifies the waiting
time for SUN2000
restart after the power
grid recovers.
The standards of
certain countries and
regions require that
the SUN2000 must
not connect to the
power grid when the
power grid voltage is
higher than the upper
limit.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Unit
Default
Value
N/A
The default
value varies
depending
on the
model. The
displayed
value
prevails.
N/A
The default
value varies
depending
on the grid
N/A
code. The
displayed
value
prevails.
N/A
The default
value varies
depending
on the grid
code. The
s
displayed
value
prevails.
V
The default
value varies
depending
on the grid
code. The
displayed
value
prevails.
Value Range
Remarks
N/A
N/A
Three-phase
This parameter is
three-wire
available only for
the
Three-phase
SUN2000-33KTL,
four-wire
SUN2000-36KTL,
and SUN2000s
whose models
include -US.
PQ mode 1
This parameter is
available only for
PQ mode 2
the
SUN2000-36KTL
and
SUN2000-42KTL.
Disable
This parameter is
set to Disable by
Enable
default if the
Japanese grid code
is selected.
[0, 900]
The value range is
[150s, 900s] if the
Japanese grid code
is selected.
[100%Vn,
136%Vn]
Vn represents the
rated voltage.